Configuring via Modbus RTU
Described in the following chapters is how you can establish the communication.
The controller is set to slave address 1 ex works (rotary switch to "1"), baud rate 19200 baud, even parity, 1 stop bit. All changes take effect only after the controller is restarted.
Communication settings
Slave address, baud rate and parity are dependent on the position of the S1 rotary switch and, if applicable, on objects 2028h, 202Ah, 202Dh.
Configuration | Object | Value range | Factory settings |
---|---|---|---|
Slave address | 2028h | 1 to 247 | 5 |
Baud rate | 202Ah | 7200 to 256000 | 19200 |
Parity | 202Dh |
|
0x04 (Even) |
- No parity: 2 stop bits
- "Even" or "Odd" parity: 1 stop bit
The following baud rates are supported:
- 7200
- 9600
- 14400
- 19200
- 38400
- 56000
- 57600
- 115200
- 128000
- 256000
You must save the changes by writing value "65766173h" in object 1010h:0Bh. The changes are not taken over until after the controller has been restarted.
Rotary switch
The PD6-E is equipped with a hex coding switch – similar to that shown in the following figure.
You can thereby determine the source for the slave address, the baud rate and the parity; the following table shows the possible combinations.
Position of the rotary switch | Slave address | Baud rate and parity | |
---|---|---|---|
dec | hex | ||
0 | 0 | Object 2028h | Object 202Ah or 202Dh |
1-14 | 1-E | Number of the rotary switch | Object 202Ah or 202Dh |
15 | F | 5 | 19200, even Parity |