2037h Open Loop Current Reduction Value/factor Function This object specifies the value as root mean square (RMS) to which the current must be reduced when current reduction is activated in open loop and the motor is idling. Object description Index 2037h Object Name Open Loop Current Reduction Value/factor Object Code VARIABLE Data type INTEGER32 Saveable yes, category: application Access Read/write PDO Mapping No Admissible Values Specified Value FFFFFFCEh Firmware Version FIR-v1426 Change History Description Value of 2037h greater/equal 0 and smaller than value in 2031h The current is reduced to the value entered in object 2037h. The value is in mA and used as root mean square (RMS). Value of 2037h is between -1 and -100 The value in 2037h is interpreted as the percentage reduction factor relative to 2031h. Example: Object 2031h was set to 4200 mA. The value -60 in object 2037h will reduce the current as root means square (RMS) up to 60 % in comparison to 2031h. As a result you'll get a current reduction down to 2031h * (2037h + 100) / 100 = 1680 mA. The value "-100" in 2037h as a further example will reduce the current reduction to 0 mA.
2037h Open Loop Current Reduction Value/factor Function This object specifies the value as root mean square (RMS) to which the current must be reduced when current reduction is activated in open loop and the motor is idling. Object description Index 2037h Object Name Open Loop Current Reduction Value/factor Object Code VARIABLE Data type INTEGER32 Saveable yes, category: application Access Read/write PDO Mapping No Admissible Values Specified Value FFFFFFCEh Firmware Version FIR-v1426 Change History Description Value of 2037h greater/equal 0 and smaller than value in 2031h The current is reduced to the value entered in object 2037h. The value is in mA and used as root mean square (RMS). Value of 2037h is between -1 and -100 The value in 2037h is interpreted as the percentage reduction factor relative to 2031h. Example: Object 2031h was set to 4200 mA. The value -60 in object 2037h will reduce the current as root means square (RMS) up to 60 % in comparison to 2031h. As a result you'll get a current reduction down to 2031h * (2037h + 100) / 100 = 1680 mA. The value "-100" in 2037h as a further example will reduce the current reduction to 0 mA.
Function This object specifies the value as root mean square (RMS) to which the current must be reduced when current reduction is activated in open loop and the motor is idling.
Object description Index 2037h Object Name Open Loop Current Reduction Value/factor Object Code VARIABLE Data type INTEGER32 Saveable yes, category: application Access Read/write PDO Mapping No Admissible Values Specified Value FFFFFFCEh Firmware Version FIR-v1426 Change History
Description Value of 2037h greater/equal 0 and smaller than value in 2031h The current is reduced to the value entered in object 2037h. The value is in mA and used as root mean square (RMS). Value of 2037h is between -1 and -100 The value in 2037h is interpreted as the percentage reduction factor relative to 2031h. Example: Object 2031h was set to 4200 mA. The value -60 in object 2037h will reduce the current as root means square (RMS) up to 60 % in comparison to 2031h. As a result you'll get a current reduction down to 2031h * (2037h + 100) / 100 = 1680 mA. The value "-100" in 2037h as a further example will reduce the current reduction to 0 mA.